21
Checking and adjusting the ignition and ionisation electrodes
13
±1
6
+2
0
3
+2 0
14
±1
A
Ignition electrodes
B
Ionisation electrode
C
Up to 35 kW
D
From 45 kW
1.
Check the electrodes for wear and
contamination.
2.
Clean the electrodes with a small
brush (not with a wire brush) or sand-
paper.
!
Please note
Wire gauze:
Do not damage.
3.
Check the electrode gaps. If the gaps
are not as specified or the electrodes
are damaged, replace and align the
electrodes together with new gas-
kets. Tighten the electrode fixing
screws with 2.5 Nm.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 860 GB