23
– Only use solvent-free cleaning
agents. Ensure that no cleaning
agents enter between the boiler
body and the thermal insulation.
– Remove soot deposits with alka-
line cleaning agents with addi-
tional surfactants (e.g. Fauch
600).
– Remove coatings and surface
discolouration (yellow-brown)
with slightly acidic, chloride-free
cleaning agents based on phos-
phoric acid (e.g. Antox 75 E).
2.
Remove loose deposits from the
boiler; flush the heating surfaces and
the flue gas collector thoroughly with
a water jet.
Danger
Loose residues and residual
cleaning agents can lead to
injury.
Wear goggles, protective gloves
and protective clothing.
Cleaning agent manufacturer's
details.
Note
"Fauch 600" and "Antox 75 E"
Manufacturer:
Hebro Chemie GmbH
Rostocker Straße 40
D -41199 Mönchengladbach
Cleaning and reconnecting the condensate drain system
Flue box, condensate drain, siphon, neutralising system and all hoses or pipe runs
in between are considered part of the condensate drain system.
Note
Clean the inside of the condensate drain
system at least annually.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)