56
Note
■ The codes are displayed as plain text.
■ Codes that have no function due to the
heating system equipment level or the
setting of other codes are not dis-
played.
■ Heating systems with one heating cir-
cuit without mixer and one or two heat-
ing circuits with mixer:
The heating circuit without mixer is
designated "Heating circuit 1" and
the heating circuits with mixer as
"Heating circuit 2" or "Heating cir-
cuit 3".
If the heating circuits were given indi-
vidual designations, the selected des-
ignation and "HC1", "HC2" or "HC3"
appear instead.
1.
Press
OK
and
å
simultaneously
for approx. 4 s.
2. "Coding level 1"
3.
Select group of required coding
address:
■
"General"
■
"Boiler"
■
"DHW"
■
"Solar"
■
"Heating circuit 1/2/3"
■
"All cod. or solar"
In this group, all coding addresses
from coding level 1 (except the cod-
ing addresses from the
"Solar"
group) are displayed in ascending
order.
4.
Select coding address.
5.
Select value according to the follow-
ing tables and confirm with
OK
.
6. If you want to reset all codes to
their delivered condition:
Select
"Standard setting"
in
"Cod-
ing level 1"
.
Note
This also resets codes from coding
level 2.
Code 1
Calling up coding level 1
5692 860 GB