64
Parameter
address b5:...
With heating circuit pump logic function:
Heating circuit pump "Off"
Heating circuit pump "On"
1
RT
actual
> RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
> RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
> RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
> RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
> RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
> RT
set
RT
actual
< RT
set
- 1 K
7
RT
actual
> RT
set
- 1 K
RT
actual
< RT
set
- 2 K
8
RT
actual
> RT
set
- 2 K
RT
actual
< RT
set
- 3 K
Coding in the delivered condition
Possible change
Flow temperature minimum limit
C5:20
Electronic minimum flow
temperature limit 20 °C
C5:1
to
C5:127
Minimum limit adjustable
from 1 to 127 °C (limited by
boiler-specific parameters)
Flow temperature maximum limit
C6:74
Electronic maximum flow
temperature limit set to
74 °C
C6:10
to
C6:127
Maximum limit adjustable
from 10 to 127 °C (limited
by boiler-specific parame-
ters)
Heating program - changeover
d5:0
External heating program
changeover changes to
"Constant operation with
reduced room tempera-
ture" or "Standby mode"
d5:1
The external heating pro-
gram changeover changes
to "Constant operation with
standard room tempera-
ture" (subject to coding
address 3A, 3b and 3C)
Ext. heating program changeover to heating circuit
d8:0
No heating program
changeover via extension
EA1
d8:1
Heating program change-
over via input DE1 at exten-
sion EA1
d8:2
Heating program change-
over via input DE2 at exten-
sion EA1
d8:3
Heating program change-
over via input DE3 at exten-
sion EA1
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5692 860 GB