72
Coding in the delivered condition
Possible change
DHW circulation pump run-
time adjustment: Coding
address 3d
3d:5
DHW circulation pump
runtime for brief opera-
tion: 5 min
3d:1
to
3d:60
DHW circulation pump run-
time adjustable from 1 to
60 min
52:0
Never adjust
53:0
Function, connection A1
at internal extension H1:
Central fault message
54:0
Without solar thermal
system
54:1
With Vitosolic 100 (auto-
matic recognition)
54:2
With Vitosolic 200 (auto-
matic recognition)
54:4
With solar control module
SM1 with auxiliary function,
e.g. central heating backup
(automatic recognition)
6E:50
Never adjust
76:0
Without LON communi-
cation module
76:1
With LON communication
module (automatic recog-
nition)
77:1
LON subscriber number,
if a LON communication
module is installed
77:2
to
77:99
LON subscriber number,
adjustable from 1 to 99:
1 = Boiler
2 - 5 = Never adjust
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Assign each number once
only.
79:1
With LON communication
module: Control unit is
fault manager
79:0
Control unit is not fault
manager
7b:1
With LON communication
module: Control unit
transmits the time
7b:0
Does not transmit time
7F:1
Detached house
7F:0
Apartment building
Code 2
General
(cont.)
5692 860 GB