74
Coding in the delivered condition
Possible change
95:0
Without Vitocom 100
communication interface
95:1
With Vitocom 100 commu-
nication interface (auto-
matic recognition)
97:0
With LON communication
module: The outside tem-
perature of the sensor
connected to the control
unit is utilised internally
97:1
Control unit receives the
outside temperature
97:2
Control unit transmits the
outside temperature to the
Vitotronic 200-H
98:1
Viessmann system num-
ber (in conjunction with
monitoring several sys-
tems via Vitocom 300)
98:1
to
98:5
System number adjustable
from 1 to 5
99:0
Never adjust
9A:0
Never adjust
9b:70
Set flow temperature for
external demand 70 °C
9b:0
to
9b:127
Set flow temperature for
external demand adjusta-
ble from 0 to 127 °C (limited
by boiler-specific parame-
ters)
9C:20
Monitoring LON subscrib-
ers.
If a subscriber fails to
respond, the values
specified inside the con-
trol unit will be used after
20 min. Only then will a
fault message be issued.
9C:0
No monitoring
9C:5
to
9C:60
Time adjustable from 5 to
60 min
9F:8
Differential temperature
8 K; only in conjunction
with a mixer circuit
9F:0
to
9F:40
Differential temperature
adjustable from 0 to 40 K
Code 2
General
(cont.)
5692 860 GB