89
Coding in the delivered condition
Possible change
d8:0
No heating program
changeover via extension
EA1
d8:1
Heating program change-
over via input DE1 at exten-
sion EA1
d8:2
Heating program change-
over via input DE2 at exten-
sion EA1
d8:3
Heating program change-
over via input DE3 at exten-
sion EA1
E1:1
Never adjust
E2:50
With remote control: No
display correction of the
actual room temperature
E2:0
to
E2:49
Display correction –5 K
to
Display correction –0.1 K
E2:51
to
E2:99
Display corr0.1 K
to
Display corr4.9 K
E5:0
Never adjust
F1:0
Screed function disabled F1:1
to
F1:6
Screed function adjustable
in accordance with 6
optional temperature/time
profiles (see page 120)
F1:15
Constant flow temperature
20 °C
F2:8
Time limit for party mode
or external heating pro-
gram changeover via key:
8 h
*1
F2:0
No time limit for party
mode
*1
F2:1
to
F2:12
Time limit adjustable from 1
to 12 h
*1
F8:-5
Temperature limit for ter-
minating reduced mode
-5 ºC, see example on
page 122.
Observe the setting of
coding address "A3"
F8:+10
to
F8:-60
Temperature limit adjusta-
ble from
+10 to -60 °C
F8:-61
Function disabled
F9:-14
Temperature limit for rais-
ing the reduced set room
temperature -14 ºC, see
example on page 122
F9:+10
to
F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjusta-
ble from
*1
Party mode ends automatically in the "Heating and DHW" program, when the
system changes over to operation with standard room temperature.
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5692 860 GB