69
Parameter address
b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
6
RT
actual
> RT
set
RT
actual
< RT
set
–
1 K
7
RT
actual
> RT
set
–
1 K
RT
actual
< RT
set
–
2 K
8
RT
actual
> RT
set
–
2 K
RT
actual
< RT
set
–
3 K
Coding in the delivered condition
Possible change
Min. flow temperature heating circuit
C5:20
Electronic minimum flow tempera-
ture limit 20 °C
C5:1
to
C5:127
Minimum limit adjustable from 1 to
127 °C (limited by appliance-specific
parameters)
Max. flow temperature heating circuit
C6:74
Electronic maximum flow tempera-
ture limit set to 74 °C
C6:10
to
C6:127
Maximum limit adjustable from 10 to
127 °C (limited by appliance-specific
parameters)
Heating program changeover
d5:0
External operating program
changeover switches the operating
program to "Constant operation at
reduced room temperature" or
"Standby mode"
d5:1
The external operating program
changeover switches to "Constant
operation at standard room tempera-
ture" (subject to coding address 3A,
3b and 3C)
Ext. heating program changeover to heating circuit
d8:0
No operating program changeover
via EA1 extension
d8:1
Operating program changeover via
input DE1 at EA1 extension
d8:2
Operating program changeover via
input DE2 at EA1 extension
d8:3
Operating program changeover via
input DE3 at EA1 extension
Max. pump speed in standard mode
E6:...
Only for heating systems without a
heating circuit with mixer:
Maximum speed of the variable
speed secondary pump as a % of
the max. speed in standard mode.
Value is determined by appliance-
specific parameters.
E6:0
to
E6:100
Maximum speed adjustable from 0
to 100 %
Min. pump speed
E7:50
Only for heating systems without a
heating circuit with mixer:
Minimum speed of the variable
speed secondary pump:
50 % of the max. speed
E7:0
to
E7:100
Minimum speed adjustable from 0 to
100 % of maximum speed
Screed drying
F1:0
Screed drying not active
F1:1
to
F1:6
Screed drying adjustable with choice
of 6 temperature/time profiles (see
page 145)
F1:15
Constant flow temperature 20 °C
Code 1
"Heating circuit"
(cont.)
5678 044 GB
Codes
Summary of Contents for D2RA
Page 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Page 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Page 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Page 163: ...163 5678 044 GB ...