Raising the reduced room temperature
During operation at reduced room temperature, the
reduced set room temperature can be automatically
raised subject to the outside temperature. The temper-
ature is raised in accordance with the selected heating
curve, and no higher than the standard set room tem-
perature.
The outside temperature limits for the start and end of
temperature raising can be set in coding addresses
"F8" and "F9" in the
"Heating circuit"
group.
Example
A
B
-20
Outside temperature in °C
Boiler
water
temperature/
flow temperature
in °C
80
70
60
50
40
30
0
-5
-10
-15
5
10
Set room temperature
in °C
35
30
25
20
15
10
5
0
90
Fig. 96
A
Heating curve for operation at standard room tem-
perature
B
Heating curve for operation at reduced room tem-
perature
Reducing the heat-up time
During the transition from operation at reduced room
temperature to operation at standard room tempera-
ture, the flow temperature will be raised in accordance
with the selected heating curve. The flow temperature
increase can be raised automatically.
The value and duration of the additional increase in set
flow temperature can be set in coding addresses "FA"
and "Fb" in the
"Heating circuit"
group.
Function description
Control functions
(cont.)
5678 044 GB
Functions
Summary of Contents for D2RA
Page 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Page 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Page 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Page 163: ...163 5678 044 GB ...