50
Display
Action
Automatic calibration of the combustion
controller
No
Fault E3
Ensure adequate
heat transfer. Press
reset button
R
.
Fault Eb
Check gap between
ionisation electrode
and burner gauze
assembly.
Check allocation of
gas type (coding ad-
dress 82, gas train
setting).
Check flue system;
remove flue gas re-
circulation if re-
quired.
Press reset button
R
.
For further details regarding faults, see page 91.
Checking the balanced flue system for tightness (annular gap check)
A
Fig. 34
A
Combustion air aperture (ventilation air)
For balanced flue systems tested together with the
heat source, there is no requirement for a tightness
test (overpressure test) during commissioning by the
flue gas inspector.
In this case, we recommend that your heating contrac-
tor carries out a simple tightness test during the com-
missioning of your system. For this it would be suffi-
cient to check the CO
2
or O
2
concentration in the com-
bustion air at the annular gap of the balanced flue
pipe.
If the CO
2
concentration is less than 0.2 % or the O
2
concentration is greater than 20.6 %, the flue pipe is
deemed to be sufficiently gas tight.
If actual CO
2
values are higher or actual O
2
values are
lower, a pressure test with a static pressure of 200 Pa
will need to be carried out on the flue pipe.
Commissioning, inspection, maintenance
Function sequence and possible faults
(cont.)
5678 044 GB