Fig. 6
A
Power supply, extension (electronics module)
B
Power supply for heat generator
C
Power supply 1/N/PE, 230 V/50 Hz
D
Fuse (max. 16 A)
E
Mains isolator, 2-pole, on site
F
Junction box (on site)
Connect the power supply in accordance with the dia-
gram.
If the power supply to the appliance is connected with
a flexible cable, ensure that the live conductors are
pulled taut before the earth conductor in the event of
strain relief failure. The length of the earth conductor
wire will depend on the design.
Danger
Incorrect core assignment can result in serious
injury and damage to the appliance.
Never interchange cores "L" and "N".
!
Please note
Incorrect phase sequence can cause damage to
the appliance.
Ensure phase equality with the heat generator
power supply.
Colour coding to IEC 60757
BN
Brown
BU
Blue
GNYE Green/yellow
Installation sequence
Power supply
(cont.)
6151
118
Installation