118
Control unit
message
System characteristics
Cause
Measures
F.195/12F0
No power generation
Combustion control CO
content outside tolerance
range
■
Check gas type setting, correct if
required.
■
Check balanced flue system for:
–
Flue gas recirculation
–
Leaks
■
Check ventilation air supply for
ingress of flue gas due to non-
compliance with chimney clear-
ances, e.g. by a solid fuel boiler.
If fault recurs, notify Viessmann
Technical Service.
Note
Reset the message on the fuel cell
module programming unit.
Then switch the ON/OFF switch of
the fuel cell module OFF for ap-
prox. 10 s and ON again.
F.196/13F0
No power generation
Flammable gases sensor
has responded.
■
Check balanced flue system for:
–
Flue gas recirculation
–
Leaks
■
Check ventilation air supply for:
–
Ingress of flue gas due to non-
compliance with chimney clear-
ances, e.g. by a solid fuel boil-
er
–
Outgassing/contamination in
the air supply system (e.g. sili-
cones, oils, paints, detergents,
deposits, etc.)
If the fault message appears dur-
ing initial commissioning: Immedi-
ately close the gas shut-off valve
on the fuel cell module or the gas
shut-off valve for the entire unit.
Notify Viessmann Technical Serv-
ice.
Before commissioning, the flam-
mable gases sensor
must
be re-
placed.
Note
The fault message can only be re-
set on the programming unit of the
fuel cell module.
F.198/17F0
No power generation
Fault, reformer burner ig-
nition
Reset the fault once.
If the fault recurs, notify Viessmann
Technical Service.
F.199/19F0
No power generation
Fault, reformer burner ig-
nition
Reset the fault once.
If the fault recurs, notify Viessmann
Technical Service.
Troubleshooting
Fault messages on the gas condensing…
(cont.)
5853335
Diagnosis