135
Message, con-
trol unit / fuel
cell
System characteristics
Cause
Measures
P.1
—
Interval until the next serv-
ice
Perform maintenance.
P.4
—
System pressure too low
Top up heating water
P.5/05F0
No power generation
5-yearly fuel cell service
required
Carry out the 5-yearly service.
Note
The message can
only
be cleared
on the programming unit of the fuel
cell module.
P.6/07F0
No power generation
Repairs required
Carry out repairs.
Note
The message can
only
be cleared
on the programming unit of the fuel
cell module.
P.7/09F0
No power generation
Decommissioning re-
quired (after 20 years of
operation)
Carry out decommissioning.
P.8
—
Interval in burner hours
gas condensing module
until the next service
Perform maintenance.
P.14
—
Fuel cell maintenance re-
quired in less than
45 days
Perform maintenance.
P.15
—
Fuel cell maintenance re-
quired in less than
1 month
Perform maintenance.
P.19
—
Fuel cell overhaul required
in less than 3 month
—
P.20
—
Fuel cell overhaul required
in less than 2 month
—
P.22
—
Fuel cell overhaul required
in less than 1 month
—
P.23
—
6 months until fuel cell de-
commissioning
—
P.24
—
5 months until fuel cell de-
commissioning
—
P.25
—
4 months until fuel cell de-
commissioning
—
P.26
—
3 months until fuel cell de-
commissioning
—
P.27
—
2 months until fuel cell de-
commissioning
—
P.29
—
1 month until fuel cell de-
commissioning
—
Troubleshooting
Service messages
5853335
Diagnosis