Fault E3
Ensure adequate
heat transfer.
Press reset button
R
.
Fault Eb
Check gap
between ionisation
electrode and
burner gauze
assembly.
Check allocation of
gas type (coding
address 82, gas
train setting).
Check flue system;
remedy flue gas
recirculation if
required.
Press reset button
R
.
For further details regarding faults, see
page 103.
Checking the static and supply pressure
Danger
CO build-up as a result of an incorrect burner setup can have serious health
implications.
Carry out a CO test prior to and after work on gas equipment.
Operation with LPG
Flush the LPG tank twice during commissioning/replacement. Vent the tank and gas
supply lines thoroughly after flushing.
Commissioning, inspection, maintenance