58
Flow temperature sensor M3
qW
Heating circuit pump M3
qE
Extension kit for one heating circuit
with mixer M3
qR
Low loss header
qT
Flow temperature sensor, low loss
header
wP
Solar collectors
wQ
Collector temperature sensor
Function/system components
Code
Adjust Delivered con-
dition
Operation with LPG
82:1
82:0
System
only
with two heating circuits with mixer with
extension kit for mixer with DHW heating
00:8
00:10
System
without
DHW circulation pump:
Heating circuit pump A1 connection at extension
AM1, terminal A1
—
33:1
System
with
DHW circulation pump:
Heating circuit pump A1 connection at extension
AM1, terminal A1
—
33:1
DHW circulation pump connection at extension AM1,
terminal A2
—
34:0
System with low loss header
04:0
04:1
Adjusting the heating curves
The heating curves illustrate the relation-
ship between the outside temperature
and the boiler water or flow tempera-
ture.
To put it simply, the lower the outside
temperature, the higher the boiler water
or flow temperature.
The room temperature, again, depends
on the boiler water or the flow tempera-
ture.
Note
If the heating system includes heating
circuits with mixers, then the flow tem-
perature of the heating circuit without
mixer is higher by a selected differential
(8 K in the delivered condition) than the
flow temperature of the heating circuits
with mixers.
The differential temperature can be
changed at coding address 9F.
Settings in the delivered condition:
■ Slope = 1.4
■ Level = 0
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)