60
Changing the slope and level
A
B
Boiler water or flow temperature in °C
90
+20
-20
Outside temperature in °C
3.5
1.4
0.2
A
Changing the slope
B
Changing the level (vertical parallel
offset of the heating curve)
Extended menu:
1.
å
2. "Heating"
3.
Select heating circuit.
4. "Heating curve"
5. "Slope"
or
"Level"
6.
Select heating curve according to the
system requirements.
Adjusting the set room temperature
Standard room temperature
90
-20
26 + 20
A
C
D
E
B
Example 1: Adjustment of the standard
room temperature from 20 to 26°C
A
Boiler water temperature or flow
temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Adjustment of the standard room
temperature:
Operating instructions
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB