48 °C
Heating
Boiler temperature
Select with
(
Heating mode
The control unit determines a set boiler
water temperature subject to outside
temperature or room temperature (if a
room temperature-dependent remote
control is connected) and to the slope/
level of the heating curve.
The determined set boiler water temper-
ature is transferred to the burner control
unit. From the set and actual boiler water
temperatures, the burner control unit cal-
culates the modulation level and regu-
lates the burner accordingly.
The electronic temperature limiter inside
the burner control unit limits the boiler
water temperature.
Heating the DHW primary cylinder from cold
The heating circuit pump is switched ON
and the three-way diverter valve will be
changed over, if the cylinder tempera-
ture sensor captures a temperature
lower than the defaulted set tempera-
ture.
■ The cylinder primary pump is switched
ON if the boiler water temperature
≥
set DHW temperature.
■ The burner is switched ON if the boiler
water temperature
≤
set DHW temper-
ature, and the cylinder primary pump
is switched ON when the required
boiler water temperature is reached.
Function description
Control unit
5412 755 GB