18
5443 109 v1.9
Pyrot Technical Data
Mechanical
De-ashing in Base Container
Description
De-ashing in Base Container (for Pyrot KRT-150)
De-ashing in Base Container (for Pyrot KRT-220)
De-ashing in Base Container (for Pyrot KRT-300)
De-ashing in Base Container (for Pyrot KRT-400)
De-ashing in Base Container (for Pyrot KRT-540)
Complete de-ashing by auger of the fire box ash chamber
into the maximum volume base container situated under
the boiler. A light barrier control system keeps the ash
level over the auger even. As a result, the ash in the ash
chamber under the gasification system can burn out,
and in normal operation only cool ash that has burned
out is conveyed into the container. With the large base
container, maximum maintenance-free intervals are
achieved.
Supplied with:
- Boiler ash chamber with ash level control system and
de-ashing auger made of high-temperature steel;
powered by a worm drive motor
- Base container with maximum volume and two
maintenance doors for removing ash by vacuum or rake
- Control of the de-ashing by light barrier
Boiler Model KRT-
150
220
300
400
540
Dimensions
f
in (mm)
29
1/8
(740)
29
1/8
(740)
34
5/8
(880)
37
13/16
(960)
43
1/8
(1096)
g
in (mm)
17
11/16
(450)
20
3/16
(513)
31 (787)
17
15/16
(456)
21
11/16
(551)
i
in (mm)
23
3/8
(593)
26¾ (680)
26¾ (680)
31½ (800)
31½ (800)
Volume of base container
USG (L)
63 (240)
95 (360)
100 (380)
158.5 (600)
185 (700)
Weight of complete de-ashing system
(in addition to boiler weight)
lb (kg)
705 (320)
749 (340)
793 (360)
838 (380)
882 (400)
Data and dimensions for de-ashing in base container