13
Burner output
in kW
Permissible CO
2
content in %
80
9.0 to 9.5
105 to 130
8.7 to 9.2
3.
If the CO
2
content has to be adjus-
ted:
Turn adjusting screw "V"
A
(2.5 mm Allen key) until the CO
2
con-
tent is within the specified range.
4.
Record the actual value in the report
(on page 45).
CO
2
test at the lower output
A
B
C
D
E
1.
Press "-"
C
until the service display
has decremented to "00" (lower out-
put).
2.
Check the CO
2
content at the flue
pipe.
Burner output
in kW
Permissible CO
2
content in %
80
8.5 to 9.0
105 to 130
8.0 to 8.5
3.
If the CO
2
content has to be adjus-
ted:
Turn adjusting screw "N"
A
in small
increments (2.5 mm Allen key) until
the CO
2
content lies within the speci-
fied range.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)