14
4.
Record the actual value in the report
(on page 45).
Rechecking the values
Ramp up and down to the upper and
lower outputs again using the pro-
gramming unit in the burner control
unit. If the values do not match the
permissible CO
2
content according to
the table on pages 13 and 13, repeat
the steps for the upper and lower out-
put.
5.
Press "S"
D
and "-"
C
simultane-
ously. The burner is now in operating
mode.
Checking the ionisation current
A
C
D
B
0
1.
Switch OFF the main isolator.
0
2.
Pull off ionisation current cable plug
C
.
0
3.
Switch ON the main isolator.
There must be a fault shutdown
after two burner starts have been
attempted. Fault code "F 25" flashes
in display
A
.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 488 GB