Set-up
8
Burner Set-up - Gas
(continued)
Verifying input of gas boilers
Natural gas burners must have gas
input clocked using the gas meter.
Ensure there is no gas flowing through
the meter other than to the gas-fired
boiler being checked. See pages 15 and
16 for gas flow rate and values for time
(in seconds) for clocking gas meter.
Clock at least 10 revolutions on a one
ft
3
gas meter dial and divide time by
10. The value arrived at should be the
same as shown on pages 15 and 16.
If necessary, manifold pressure must be
adjusted to make sure burner is firing at
nominal input. Do not exceed gas input
stated on rating plate. Turn adjustment
screw on gas pressure regulator (RV52)
clockwise to increase gas flow, and
counterclockwise to decrease gas flow
(as per instructions on the previous
page).
If checking gas input with a manometer
only use manifold pressures given in
manual as a starting point, and use
combustion instruments to ensure safe
and efficient combustion values.
Be sure to turn gas off before attaching
or removing pressure taps. All plugs
removed for the purpose of gas
pressure measurements must be
replaced and leak-tested after
measurements.
Replacement of 24V gas valve
Use only replacement gas valves from
Viessmann Manufacturing. The 24 VAC
Dungs ¾” MVD-LE 207/6 and ½”
MVD-LE 205/6 direct spark valves are
special valves designed to operate at
the low manifold pressures required by
the Riello burner for both natural and
propane gas. Do
not
use other gas
valve unless specified by Viessmann.
Field measured combustion results
Use the combustion data label packed
with the gas burner to record field
measured combustion results and affix
label to gas burner.
Adjustment data tag
ANSI Z21-17b-1994
Input: C.F.H.
Manifold pressure
Air damper
Air/gas ratio No.
Flue gas temp.
O
2
level: %
CO
2
level: ppm
Date
Completed by
Installing
contractor
It is necessary to follow all safety
information in the Riello technical
literature as well as all other OEM
component instructions shipped with
this manual. The Viessmann factory
settings are an initial guide to be
verified or changed by the installer
based on field measured combustion
results. The burner settings arrived at
during field measurements may be
different from the generalized
conversion burner settings given in the
Riello technical literature.
5
2
6
5
6
6
5
v
2
.5
IMPORTANT
Each Riello gas burner has a different
manifold pressure. When replacing a
gas valve, a manometer and
instruments measuring combustion
must be used to ensure burner is
operating safely at its designed input.
An overfired burner is unsafe and can
cause severe personal injury or loss
of life if products of combustion are
allowed to enter living space through
incorrect procedures.
WARNING
Checking for a safe concentration of
carbon monoxide (below 50 ppm
air-free) will ensure continual safe
operation of boiler and burner. Annual
maintenance and cleaning as
described in this manual must be
done. Failure to heed this warning
may lead to severe personal injury or
loss of life.
WARNING
IMPORTANT
Summary of Contents for Riello
Page 21: ...Appendix 21 Notes 5265 665 v2 5...