12
en-US/C
A
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory setting
Change to
Description
Page
tLB
2 min
Loading break time
48
tRUN
15 min
Circulation runtime
48
PSPEE
OFF
Pause speed option
51
PDELA
OFF
Pump delay option
51
COOL >
Cooling functions
OSYC*
OFF
System cooling
51
OSTC
OFF
Tank cooling
52
OHDP*
OFF
Heat dump
52
DT4 >
Heat exchange
DT4O
6.0 K [12.0 °Ra]
Switch-on difference
52
DT4F
4.0 K [8.0 °Ra]
Switch-off difference
52
DT4S
10.0 K [20.0 °Ra]
Set difference
RIS4
2 K [4 °Ra]
Rise
MAX4O
60.0 °C [140.0 °F]
Switch-on temperature (maximum limitation)
MAX4F
58.0 °C [136.0 °F]
Switch-off temperature (maximum limitation)
MIN4O
5.0 °C [40.0 °F]
Switch-on temperature (minimum limitation)
MIN4F
10.0 °C [50.0 °F]
Switch-off temperature (minimum limitation)
OTH >
Thermostat function option
56
PUMP >
Speed
PUMP1
OnOF
Speed variant pump 1
45
PUMP2
OnOF
Speed variant pump 2
45
PUMP3
OnOF
Speed variant pump 3
45
MAN >
Manual mode
MAN1
Auto
Manual mode 1
56
MAN2
Auto
Manual mode 2
56
MAN3
Auto
Manual mode 3
56
MAN4
Auto
Manual mode 4
56
BLPR >
OFF
Blocking protection
56
OTDIS >
OFF
Thermal disinfection option
57
OPARR >
OFF
Parallel relay option
58
OHQM >
OFF
Energy metering option
58
DATE>
Enter date
60
LANG >
dE
Language
61
UNIT >
°C
Unit
60
OSDC >
SD card option
61
CODE
0000
User code
RESET
OFF
Factory setting
* are blocked against each other
Summary of Contents for SCU345