39
yes
Automatic calibra-
tion of the com-
bustion controller
no
Fault E3
Ensure adequate
heat transfer.
Press reset button
R
.
Fault Eb
Check gap be-
tween ionisation
electrode and
burner gauze as-
sembly.
Check allocation of
gas type (coding
address 82, gas
train setting).
Check flue sys-
tem; remedy flue
gas recirculation if
required.
Press reset button
R
.
For further details regarding faults, see
page 117.
Checking the static and supply pressure
Danger
CO build-up as a result of incor-
rect burner adjustment can have
serious health implications.
Carry out a CO test before and
after work on gas appliances.
Operation with LPG
Flush the LPG tank twice during com-
missioning or replacement. Vent the tank
and gas supply line thoroughly after
flushing.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service