61
Connecting the control unit to the LON
The LON communication module must
be plugged in.
Note
The data transfer via the LON can take
several minutes.
Single boiler system with
Vitotronic 200-H and Vitocom 300
(example)
Set the LON subscriber numbers and
further functions via code 2 in group
"General"
(see following table).
Note
In the LON system, the same subscriber
number cannot be allocated twice.
Only one Vitotronic may be program-
med as fault manager.
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
LON
LON
LON
Subscriber no. 1
Code "77:1"
Subscriber no. 10
Code "77:10"
Subscriber no. 11
Set
code "77:11"
Subscriber no.
99
Control unit is fault
manager
Code "79:1"
Control unit is not
fault manager
Code "79:0"
Control unit is not
fault manager
Code "79:0"
Device is fault
manager
Control unit transmits
the time
Code "7b:1"
The control unit re-
ceives the time
Set
code "81:3"
The control unit re-
ceives the time
Set
code "81:3"
Device re-
ceives the
time
Control unit transmits
outside temperature
Set
code "97:2"
Control unit receives
outside temperature
Set
code "97:1"
Control unit receives
outside temperature
Set
code "97:1"
—
LON subscriber fault
monitoring
Code "9C:20"
LON subscriber fault
monitoring
Code "9C:20"
LON subscriber fault
monitoring
Code "9C:20"
—
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service