92
Select
"DHW"
for weather-compensated control units (see page 80).
Select
"3"
for constant temperature control units (see page 80).
Coding
Coding in the delivered condition
Possible change
56:0
Set DHW temperature
adjustable from 10 to
60 °C
56:1
Set DHW temperature ad-
justable from 10 to over
60 °C
Note
Maximum value subject to
boiler coding card.
Observe the max. permis-
sible DHW temperature.
58:0
Without auxiliary function
for DHW heating
58:10
to
58:60
Input of a second set DHW
temperature, adjustable
from 10 to 60 °C (observe
coding addresses "56" and
"63")
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable
from 1 to 10 K below the set
value
5b:0
DHW cylinder directly
connected to the boiler
5b:1
DHW cylinder connected
downstream of the low loss
header
5E:0
Circulation pump for cyl-
inder heating stays in
control mode at signal
"External blocking"
5E:1
Circulation pump for cylin-
der heating stops at signal
"External blocking"
5E:2
Circulation pump for cylin-
der heating starts at signal
"External blocking"
5F:0
Circulation pump for cyl-
inder heating stays in
control mode at signal
"External demand"
5F:1
Circulation pump for cylin-
der heating stops at signal
"External demand"
5F:2
Circulation pump for cylin-
der heating starts at signal
"External demand"
Code 2
DHW/group "3"
5623 520 GB