39
Parameter ad-
dress B5: ...
Heating circuit pump "Off"
Heating circuit pump "On"
Summer eco function active
Summer eco function passive
5
RT
actual
>
RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
>
RT
set
RT
actual
< RT
set
−
1 K
7
RT
actual
>
RT
set
−
1 K
RT
actual
< RT
set
−
2 K
8
RT
actual
>
RT
set
−
2 K
RT
actual
< RT
set
−
3 K
Coding in the delivered condition
Possible change
Flow temperature, minimum limit
C5:20
Minimum flow temperature limit set
to 20 °C
C5:1
to
C5:100
Adjustable from 1 to 100 °C
Flow temperature, maximum limit
C6:75
Maximum flow temperature limit
set to 75 °C
C6:10
to
C6:100
Adjustable from 10 to 100 °C
Room temperature sensor, limit
C8:31
No limit for room influence
Note
Only available if a remote control
unit is connected in this heating
circuit (code A0:
≠
0) and a room
temperature hook-up is set (code
B0:
≠
0).
C8:1
to
C8:30
Room influence limit adjustable from
1 to 30 °C
Party mode, time limit
F2:8
Party mode duration limited to 8 h
F2:0
No time limit for party mode. Party
mode is deactivated when the oper-
ating program is changed to
"Heat-
ing"
.
F2:1
to
F2:12
Time limit adjustable from 1 to 12 h
Transfer heat
F3:1
This function regulates to the set
max. flow temperature of the heat-
ing circuit (code C6) when the
maximum boiler temperature is
reached.
F3:0
The
"Transfer heat"
function is dis-
abled for the selected heating circuit.
Set runtime
F4:140
The mixer valve motor runs for
140 s for the selected heating cir-
cuit.
F4:10
to
F4:254
Adjustable value in s
Code 1
Heating group
(cont.)
5684984
Codes