42
Coding
Coding in the delivered condition
Possible change
Buffer charging until, sensor
D0:1
The additional heat generator
charges the heating water buffer
cylinder up to the
1st
buffer tem-
perature sensor.
D0:0
The additional heat generator does
not
charge the heating water buffer
cylinder.
D0:2
The additional heat generator charg-
es the heating water buffer cylinder
up to the
2nd
buffer temperature
sensor.
D0:3
The additional heat generator charg-
es the heating water buffer cylinder
up to the
3rd
buffer temperature
sensor.
D0:4
The additional heat generator charg-
es the heating water buffer cylinder
up to the
4th
buffer temperature
sensor.
D0:5
The additional heat generator charg-
es the heating water buffer cylinder
up to the
5th
buffer temperature
sensor.
Buffer charging until, temperature
D1:75
The additional heat source charg-
es the heating water buffer cylinder
until a temperature of 75 °C is
reached at the selected sensor
"D0:1-5"
.
D1:50
to
D1:100
Adjustable value in °C
Start delay
D2:10
Start delay of 10 min for the addi-
tional heat generator
D2:0
to
D2:250
Adjustable value in min
Start temperature, set system temperature
D3:-10
Start temperature of the additional
heat generator. Condition for start-
ing: Actual system temperature <
set system temperature - value set
(here: 10 K)
D3:-100
to
D3:-1
Adjustable value in K
Minimum runtime
D4:5
Minimum runtime of the additional
heat generator of 5 min
D4:0
to
D4:250
Adjustable value in min
Minimum pause
D5:5
Minimum pause duration of the ad-
ditional heat generator of 5 min
D5:0
to
D5:250
Adjustable value in min
Immediate start, set system temp
D6:-20
Additional heat generator is started
without delay. Condition: Actual
system temperature < set system
temperature - value set (here:
20 K)
D6:-100
to
D6:0
Adjustable value in K
Code 1
Additional heat generator group
(cont.)
5684984
Codes