46
Coding in the delivered condition
Possible change
Screed drying
F1:0
Screed drying disabled
F1:1
to
F1:6
Screed drying in accordance with
the selectable temperature:time pro-
file (for more information, see chap-
ter "Screed drying").
Boiler group
Coding
Coding in the delivered condition
Possible change
Transfer heat from, temperature
10:100
From a boiler water temperature of
100 °C, heat is transferred via ena-
bled heating circuits. Which heat-
ing circuits are enabled for
"Trans-
fer heat"
is separately defined for
each heating circuit in code F3, in
the Heating group.
10:50
to
10:110
Setting range in °C
Minimum set system temperature
13:1
A minimum set system tempera-
ture can be set. Enable the func-
tion if the heating circuits are not
controlled by the boiler control unit.
13:0
A minimum set system temperature
cannot be set.
O2 control active
5F:1
Control via flue gas oxygen con-
tent enabled.
5F:0
Control via flue gas oxygen content
disabled
.
Emergency mode - adjust the air
damper position in the extended
menu.
Automatic system, O2 probe
F9:0
■
Lambda probe heating always
on
■
Only manual calibration of Lamb-
da probe, see chapter "Calibrat-
ing the Lambda probe"
F9:1
■
Automatic start of Lambda probe
heating
■
Calibration of Lambda probe only
manually
F9:2
■
Automatic start of Lambda probe
heating
■
Automatic calibration of Lambda
probe
O2 probe type
FF:0
Lambda probe used: Type LSM 11
Note
A LSM 11 Lambda probe is used
as standard in the Vitoligno 250-S.
FF:1
Lambda probe used: Type NGK
FF:2
Lambda probe used: Type LSU with
transducer
Code 2
Heating group
(cont.)
5684984