53
Fault code dis-
played
System characteristics
Cause
Measures
32
Control mode
Lead break, flue gas tem-
perature sensor
Check flue gas temperature sen-
sor.
33
Boiler running with fixed air
damper setting
No variation of the residu-
al oxygen content in the
flue gas over a prolonged
period
■
Check Lambda probe.
■
Recalibrate Lambda probe if nec-
essary
34
All heating circuits regulate to
0 °C outside temperature
Lead break, outside tem-
perature sensor
Check outside temperature sensor.
35
No DHW heating
Lead break, top buffer
temperature sensor
Check top buffer temperature sen-
sor.
36
Control mode
Lead break, centre buffer
temperature sensor
Check centre buffer temperature
sensor.
37
Control mode
Lead break, bottom buffer
temperature sensor
Check bottom buffer temperature
sensor.
3E
Burner blocked
Current flue gas fan speed
does not match set speed.
Check flue gas fan.
41
No heating operation, mixer
module 1
Break in lead to mixer
module 1
Check connection to mixer module
1.
42
No heating operation, mixer
module 2
Break in lead to mixer
module 2
Check connection to mixer module
2.
43
No heating operation, mixer
module 3
Break in lead to mixer
module 3
Check connection to mixer module
3.
44
No room influence from re-
mote control unit 1
No connection between
boiler and remote control
unit 1
Check KM BUS connection be-
tween boiler and remote control
unit 1.
45
No room influence from re-
mote control unit 2
No connection between
boiler and remote control
unit 2
Check KM BUS connection be-
tween boiler and remote control
unit 2.
46
No room influence from re-
mote control unit 3
No connection between
boiler and remote control
unit 3
Check KM BUS connection be-
tween boiler and remote control
unit 3.
51
No heating system control,
heating circuit 1
Short circuit, flow temper-
ature sensor, heating cir-
cuit 1
Check flow temperature sensor,
heating circuit 1.
52
No heating system control,
heating circuit 2
Short circuit, flow temper-
ature sensor, heating cir-
cuit 2
Check flow temperature sensor,
heating circuit 2.
53
No heating system control,
heating circuit 3
Short circuit, flow temper-
ature sensor, heating cir-
cuit 3
Check flow temperature sensor,
heating circuit 3.
54
No DHW heating
Short circuit, cylinder tem-
perature sensor
Check cylinder temperature sen-
sor.
55
No flow control, DHW heating Short circuit, return tem-
perature sensor, DHW
heating
Check return temperature sensor,
DHW heating.
61
No heating system control,
heating circuit 1
Lead break, flow tempera-
ture sensor, heating circuit
1
Check flow temperature sensor,
heating circuit 1.
62
No heating system control,
heating circuit 2
Lead break, flow tempera-
ture sensor, heating circuit
2
Check flow temperature sensor,
heating circuit 2.
Troubleshooting
Fault display
(cont.)
5684984
Diagnosis