57
The following actuators of the mixer modules can be switched separately depending on the module (rec-
ommended during commissioning):
Display
Explanation
"Pump On"
"Open valve"
"Close valve"
Checking sensors
Temperature in °C
Resistance
in Ω
40
30
20
10
0
-10
-20
-30
1150
1100
1050
1000
950
900
850
1200
Fig. 33
Temperature in °C
0
100
200
300
0.75
1.25
1.75
2.25
Resistance
in kΩ
A
Fig. 34
A
Data point shown: Resistance of 1078 kΩ at a temperature of 20 °C
1.
Pull out corresponding plug.
2.
Check the sensor resistance at the plug.
3.
Compare the test result with the actual temperature. For details about calling up information, see chapter
"Diagnosis".
In case of severe deviation: Check for correct installation and replace the sensor if required.
Maintenance
Carrying out an actuator test
(cont.)
5684984
Service