36
The codes are divided into groups:
■
"General"
■
"Hardware"
■
"Heating"
■
"Boiler"
■
"Buffer cylinder"
, see page 41
■
"DHW"
■
"Additional boiler"
Only available if an additional heat source has been
input in the codes.
General group
Coding
Coding in the delivered condition
Possible change
Detached house/apartment building
7F:1
Detached house, same holiday
program for all heating circuits
7F:0
Apartment building, holiday program
can be adjusted separately
Minimum temperature, buffer 1 (top)
91:0
No minimum temperature
91:1
to
91:95
If a combined heating water buffer
cylinder is installed, a minimum tem-
perature for the top of buffer cylinder
(captured by PTS 1) can be set.
Hardware group
Coding
Coding in the delivered condition
Possible change
Burner / Additional boiler (Additional heat generator)
Burner / Addition-
al boiler:No
No additional heat source available Burner / Addition-
al boiler:Burner
Burner installed on the
Vitoligno 250-S
Burner / Addition-
al boiler:Addition-
al boiler
Additional boiler installed
DHW
DHW:No
No DHW heating installed
DHW:On the mix-
er module
DHW heating is connected to the ex-
tension kit.
Heating circuit 1
Heating circuit
1:No
No heating circuit 1 installed
Heating circuit
1:On the mixer
module
Heating circuit is connected to the
extension kit.
Heating circuit 2
Heating circuit
2:No
No heating circuit 2 installed
Code only is available if heating
circuit 1 is installed.
Heating circuit
2:On the mixer
module
Heating circuit is connected to the
extension kit.
Heating circuit 3
Heating circuit
3:No
No heating circuit 3 installed
Code only is available if heating
circuits 1 and 2 are installed.
Heating circuit
3:On the mixer
module
Heating circuit is connected to the
extension kit.
Solar
Solar:No
No solar group installed
Solar:On the ex-
ternal solar mod-
ule
The solar group is connected to the
external solar control unit
(Vitosolic 100 or 200).
Code 1
Overview
5684984
Codes