41
Coding
Coding in the delivered condition
Possible change
Controlled buffer operation
50:1
Heating water buffer cylinder is
charged in control mode.
50:0
Heating water buffer cylinder is not
charged in control mode.
DHW group
Coding
Coding in the delivered condition
Possible change
DHW differential
0C:0
The differential temperature of
DHW heating (differential between
contact temperature sensor and
immersion temperature sensor) is
determined automatically.
0C:1
to
0C:20
Differential temperature is adjustable
from 1 to 20 °C
DHW return temperature
0D:10
Flow control active. Set return tem-
perature corresponds to DHW tem-
perature plus 10 °C
0D:0
Flow control deactivated. Valve is al-
ways fully open.
0D:1
to
0D:30
Flow control active. Set return tem-
perature corresponds to DHW tem-
perature plus value set in °C.
Additional heat generator group
Only available if an additional heat source is installed
(Hardware group: Code
"Burner / Additional boiler"
:
≠
No).
Code 1
Buffer cylinder group
5684984
Codes