The codes are divided into groups:
■
"General"
■
"Heating"
, see page 44
■
"Boiler"
, see page 46
■
"Buffer cylinder"
■
"DHW"
General group
Coding
Coding in the delivered condition
Possible change
Fault message output delay
80:6
Minimum fault duration of 30 s be-
fore a fault message is issued
80:0
to
80:199
Adjustable from 0 s to 995 s. 1 step
≙
5 s.
Automatic summer/wintertime changeover
81:1
Automatic summer/wintertime
changeover
81:0
Manual summer/wintertime change-
over
Outside temperature, time constant
90:128
Time constant for calculating the
altered outside temperature
21 h 20 min
90:0
to
90:199
Subject to the set value, the flow
temperature is adjusted quickly (low
values) or slowly (high values) when
the outside temperature changes.
1 step
≙
10 min
Outside temperature, offset
92:0
No outside temperature correction
92:- 10
to
92:10
Correction of the outside tempera-
ture by the value set in °C
Heating group
Select the heating circuit (
"HC1"
,
"HC2"
or
"HC3"
)
with keys
Ù
/
Ú
. Adjust the parameters separately for
each heating circuit.
Coding
Coding in the delivered condition
Possible change
DHW priority
A2:2
During cylinder heating, the mixer
closes. The heating circuit pump is
switched off.
Note
Priority control is only active when
the boiler is in load operation.
A2:0
No priority control during cylinder
heating
A2:1
During cylinder heating, the mixer
closes. The heating circuit pump is
switched off.
A2:3
During cylinder heating, the set val-
ue for the flow temperature is set to
the set value for reduced heating
mode.
Code 2
Overview
5684984
Codes