12
Connect the equipotential bonding in accordance with
the requirements stipulated by your local power supply
utility and VDE [or local] regulations.
c
Carry out the equipotential bonding in accordance
with the technical requirements stipulated by the local
power supply utility and SEV regulations.
Type SVPA 400 l: Fitting the thermal insulation
Fitting the lower thermal insulation mat
2.
1.
Fig. 8
!
Please note
The thermal insulation must not come into con-
tact with naked flames.
Exercise caution when welding and brazing.
Fitting the thermal insulation on the Vitocell without Vitotrans
Note
Ensure that no fleece remnants enter the heating
water buffer cylinder through the cylinder connections.
Installation sequence
Connecting the equipotential bonding
5548 462 GB
Installation