background image

Installation and service instructions

for contractors

VIESMANN

Vitocell 100-E/100-W
Type SVWA

Heating water buffer cylinder

VITOCELL 100-E/100-W

6150632 GB

3/2020

Please keep safe.

Summary of Contents for SVWA

Page 1: ...Installation and service instructions for contractors VIESMANN Vitocell 100 E 100 W Type SVWA Heating water buffer cylinder VITOCELL 100 E 100 W 6150632 GB 3 2020 Please keep safe ...

Page 2: ...nstallation regulations Statutory regulations for the prevention of accidents Statutory regulations for environmental protection Codes of practice of the relevant trade associations Relevant country specific safety regu lations Working on the system Isolate the system from the power sup ply e g by removing the separate fuse or by means of a mains isolator and check that it is no longer live Safegu...

Page 3: ... work Repair work Please note Repairing components that fulfil a safety function can compromise the safe operation of the system Replace faulty components only with genuine Viessmann spare parts Auxiliary components spare and wearing parts Please note Spare and wearing parts that have not been tested together with the system can compromise its func tion Installing non authorised com ponents and ma...

Page 4: ... 3 Installation sequence Cylinder installation 9 Cylinder incl immersion heater 9 Connecting the equipotential bonding 9 Fitting the cylinder temperature sensor and thermometer sensor if supplied 10 4 Commissioning service reports 11 5 Product characteristics 12 6 Accessories Specification for immersion heater 13 7 Disposal Final decommissioning and disposal 14 8 Certificates Declaration of confor...

Page 5: ...teps required during inspection Not required during inspection Steps required during maintenance Not required during maintenance Intended use The appliance is only intended to be installed and operated in sealed unvented systems that comply with EN 12828 DIN 1988 or solar thermal systems that comply with EN 12977 with due attention paid to the associated installation service and operating instruc ...

Page 6: ...e of potable water Product information Vitocell 100 E 100 W type SVWA Steel cylinder for storing heating water in combination with heat pumps and solid fuel boilers with optional electric heating immersion heater Capacity 200 l Suitable for systems to EN 12828 and DIN 4753 Vitocell 100 E Vitosilver Vitocell 100 W White System examples Available system examples See www viessmann schemes com Spare p...

Page 7: ...7 2 1 4x 5 8 9 6 7 3 4 Fig 1 Preparing for installation Unpacking and handling 6150632 Service ...

Page 8: ...he heating circuits C Clamping device 1 SPR1 for cylinder temperature sensor D Heating water flow 2 HV2 from the heat generator E Clamping device 2 SPR2 for cylinder temperature sensor F Heating water return 2 HR2 from the heating circuits G Heating water return 1 HR1 to the heat generator H Drain outlet E Preparing for installation Connections 6150632 Service ...

Page 9: ...ylinder At least one of the adjustable feet must remain fully screwed in 35 Fig 4 Never extend the adjustable feet beyond a total length of 35 mm Cylinder incl immersion heater 650 Fig 5 Installation instructions immersion heater Note Maintain the minimum clearance Note The unheated length of any threaded immersion heater installed on site must be at least 100 mm Cylinder capacity 200 l Immersion ...

Page 10: ...ensor in the clamping bracket 05 Guide the thermometer cable through the groove in the thermal insulation and the hole in the sheet steel casing 06 Secure the thermometer accessory to the wall Installation instructions for wall thermometer 07 Refit the top cover Note The recess A in the top cover is intended for the thermometer cable 08 For heating water flow temperatures in excess of 95 ºC remove...

Page 11: ...Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Commissioning service reports Commissioning service reports 6150632 Service ...

Page 12: ...12 Vitocell 100 E 100 W type SVWA Cylinder capacity l 200 Standby heat loss qB S with 45 K temperature differential kWh 24 h 1 39 Product characteristics Product characteristics 6150632 Service ...

Page 13: ... kW 2 4 6 Rated voltage 3 N PE 400 V 50 Hz Rated current A 8 7 8 7 8 7 Heat up time from 10 to 60 ºC h 4 7 2 4 1 6 Content that can be heated by the immersion heater l 163 Accessories Specification for immersion heater 6150632 Service ...

Page 14: ...stem are not part of ordi nary household waste For decommissioning the system isolate the system from the power supply and allow components to cool down where appropriate All components must be disposed of correctly Disposal Final decommissioning and disposal 6150632 Appendix ...

Page 15: ...es with the European directives and supplementary national requirements in terms of its design and operational characteristics Using the serial number the full Declaration of Con formity can be found on the following website www viessmann co uk eu conformity Certificates Declaration of conformity 6150632 Appendix ...

Page 16: ... Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com 6150632 Subject to technical modifications ...