24
Danger
Incorrectly executed electrical installations can
result in injuries from electrical current and dam-
age to the appliance.
Connect the power supply and implement all
safety measures (e.g. RCD circuit) in accord-
ance with the following regulations:
■
IEC 60364-4-41
■
VDE regulations
■
TAR low voltage VDE-AR-N-4100
■
Protect the power cable to the heat pump con-
trol unit with a fuse of max. 16 A.
Danger
The absence of system component earthing can
lead to serious injury from electric current if an
electrical fault occurs.
The appliance and pipework must be connected
to the equipotential bonding of the building.
Danger
Incorrect wiring can lead to serious injury from
electrical current and result in appliance dam-
age.
■
Route extra low voltage (ELV) leads < 42 V
separately from cables
>
42 V/230 V~.
■
Strip as little of the insulation as possible,
directly before the terminals, and bundle close
to the corresponding terminals.
■
Secure cables with cable ties.
Power cable
230 V/
50 Hz
A
B
1500
≥
Fig. 20
A
DHW heat pump
B
Power supply
The DHW heat pump is fully wired with a 3-core power
cable:
■
H05VV-F 3G 1.5
■
Colour: White
■
Cores:
L1: Brown
N:
Blue
PE: Green/yellow
A separately fused
standard socket
is required for
connection to the mains:
■
230 V/50 Hz
■
Max. fuse rating 16 A
Damaged connecting cables
If connecting cables for the appliance or accessories
are damaged, these cables must be replaced with rele-
vant special connecting cables. Use only Viessmann
cables as replacements.
Installation sequence
Connecting to the power supply
(cont.)
6136003
Installation