46
Vitocal 060-A, type
T0E-ze
T0S-ze
Draw-off profile
L
XL
*1
L
XL
*1
Performance data for outdoor air mode
to
EN 16147:2011 at A7/W10-53 (air intake temperature
7 °C/room temperature 20 °C)
Coefficient of performance
ε
(COP
DHW
)
3.23
3.37
3.23
3.37
Heat-up time
h:min
10:00
10:00
10:00
10:00
Standby loss (Pes)
W
23
25
23
25
Max. available amount of water (40 °C)
l
329.5
351.0
329.5
351.0
Performance data for recirculation air mode and re-
circulation air mode with air discharge to the out-
side
to EN 16147:2011 at A7/W10-53 (air intake tem-
perature 7 °C/room temperature 7 °C)
Coefficient of performance
ε
(COP
DHW
)
2.88
3.00
2.88
3.00
Heat-up time
h:min
11:00
11:35
11:00
11:35
Standby loss (Pes)
W
33
35
33
35
Max. available amount of water (40 °C)
l
324.5
355.0
324.5
355.0
Performance data for recirculation air mode and re-
circulation air mode with air discharge to the out-
side
to EN 16147:2011 at A15/W10-53 (air intake tem-
perature 15 °C/room temperature 15 °C)
Coefficient of performance
ε
(COP
DHW
)
3.33
3.50
3.33
3.50
Heat-up time
h:min
07:39
08:15
07:39
08:15
Standby loss (Pes)
W
22
24
22
24
Max. available amount of water (40 °C)
l
335.0
362.0
335.0
362.0
Application limits
(air intake temperature)
°C
–
5 to +35
Continuous output
for DHW heating from
10 to 45 °C
in conjunction with an external heat generator with cor-
responding output and a heating water flow rate of
3.0 m
3
/h
■
Heating water
flow temperature 90 °C
kW
—
—
40
40
l/h
—
—
982
982
■
Heating water
flow temperature 80 °C
kW
—
—
32
32
l/h
—
—
786
786
■
Heating water
flow temperature 70 °C
kW
—
—
25
25
l/h
—
—
614
614
■
Heating water
flow temperature 60 °C
kW
—
—
17
17
l/h
—
—
417
417
■
Heating water
flow temperature 50 °C
kW
—
—
9
9
l/h
—
—
221
221
*1
Calculated values.
Specification
Specification
6136003
Appendix