26
The hysteresis controller is factory-set.
The hysteresis value influences the
start and stop times for "Heating" and
"Not heating".
Example:
Set room temperature: 21 °C
Hysteresis: 0.6 °C (delivered condition).
Setting range: 0.2 to 1.0 °C.
Heating stops as soon as the actual
room temperature exceeds 21.3 °C.
Heating starts as soon as the actual
room temperature undershoots 20.7 °C.
You can change the control characteris-
tics by changing the hysteresis value.
Select a lower value if your system
responds too slowly.
1.
Open the flap.
2.
Press
twice
.
3.
With / select
"Settings"
.
4.
Confirm with
OK
.
5.
With / select
"Service"
.
6.
Confirm with
OK
.
7.
With / set the required hysteresis
value.
8.
Confirm
2 times
with
OK
.
9.
Exit the menu with .
Further adjustments
Control characteristics
5699 292 GB