Troubleshooting
Diagnosis (burner control unit LMO14. ...)
(cont.)
Fault/
characteristics
Flashing
code
red at
LMO14
Cause
Remedy
Burner sooty
Too little or too much air
Correct setting.
Check and clean
impeller.
Check boiler room
ventilation.
Insufficient chimney
draught
Check flue and flue gas
baffles
Nozzle faulty
Replace nozzle, install
correct nozzle (see
page36)
Flame tube extension
(for 15 to 33kW) or
combustion chamber
liner (for Vitola200, 40 to
63kW) is missing
Fit flame tube extension
or combustion chamber
liner
Incorrect 0−point
adjustment of blast tube
connection
Check and, if necessary,
correct blast tube
connection 0−point
adjustment (see
page15)
CO
2
content
too low
Incorrect setting
Check setting (see
page36)
Infiltrating air
Seal flue pipe at boiler
adaptor.
Retighten combustion
chamber cover screws
and those on flue outlet
cover.
Flue gas
temperature
too high
Oil consumption too
high
Match oil flow to rated
output of boiler
Boiler contaminated
Clean boiler and correct
burner adjustment
Burner
operates,
constant red
flickering light
on burner
control unit
No fault, interface
diagnosis
Press reset button >3s
5692589GB
Summary of Contents for VEK
Page 31: ...31 Parts list Parts list cont 5692 589 GB 002 001 017 005 049 009...
Page 33: ...33 Parts list Parts list cont 5692 589 GB 047 020 041 021 040 80o 80p 034 033 046 039 038...
Page 37: ...37 Appendix 5692 589 GB...
Page 39: ...39 Appendix Maint service Maint service Maint service Maint service 5692 589 GB...
Page 41: ...41 Appendix Maint service Maint service Maint service Maint service 5692 589 GB...
Page 42: ...42 Appendix 5692 589 GB...