The system can be checked using this menu. For example, in case of a fault,
you can check whether the cause has been removed. This check can only be
carried out with the relay switched OFF.
In standard mode, all monitoring inputs are "
OFF
". In case of a fault, they
change into the "
ON
" condition.
Any changes into the "
ON
" condition are saved and will be displayed in the
menu "
Information
" > "
Statistics
" > "
Fault history
".
An exception is the display in case of "
power-OFF contact
". If the power-OFF
contact operates as an N/O contact (see page 134), "
On
" means that power-
OFF is active. If the power-OFF contact operates as an N/C contact (see
page 134), "
Off
" means that the power-OFF is active.
Menu item
&
"
Device settings
"
&
"
Contractor level
"
&
"
Signal inputs
"
&
"
BACK
"
Manual control of relays and mixers
The "manual control" facility can be used to switch the relays and mixers (gen-
eric term: "actuators") for starting or testing individual components.
All control functions are disabled
as long as the "
Manual control
" menu or
one of its sub-menus is called up.
All actuators are manually controlled for as long as the programming unit flap is
open.
Upon leaving the "
Manual control
" menu (e.g. by closing the programming unit
flap), all actuators that are currently not required for standard control mode, are
switched off by the control unit, and the control sequences are restarted.
Menu item
&
"
Device settings
"
&
"
Contractor level
"
&
"
Manual control
"
The following sub-menus are available from the "
Manual control
" menu:
Menu item
&
"
Relay
"
&
"
Mixer
"
&
"
Sensor temperatures
"
&
"
System overview
"
The sub-menus "
Sensor tempera-
tures
" and "
System overview
" can
also be called up from the main menu
via "
Information
". For further infor-
mation regarding the sub-menus, see
the operating instructions.
Checking signal inputs
131
Control settings
55
92
968
GB
Service
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...