As well as the procedure described in
"system configuration" (see
page 103), the system design can be
modified at this point or additional
components and/or functions selected
or deselected.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
System definition
"
&
"System scheme"
The required procedure is described
from page 103.
Language
Adjusting the required language, see page 103.
Power-OFF contact: 1S
This setting determines whether the power-OFF contact acts as N/O ("
YES
") or
N/C ("
NO
") contact.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
System definition
"
&
"Power-OFF contact: 1S"
("
YES
",
"
NO
")
Standard setting
NO
Setting range
YES/NO
Average time; outside temperature
This parameter determines the filtering of the outside temperature by a time
constant of 22 hours (standard setting). This compensates for short-term tem-
perature fluctuations.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
System definition
"
&
"Ave. time outside temp."
(
Q
/
P
)
Standard setting
22:00 h
System design
134
Control unit settings - system definition
55
92
968
GB