The reduced temperature mode (see operating instructions) will no longer be
used, if the outside temperature drops
below
this temperature limit. The equip-
ment heats up to the temperature selected for standard operation.
Operation will continue in accordance with the selected switching times, if the
average outside temperature stays
above
this temperature limit.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
System definition
"
&
"Temperature limit for red. BA"
(
1
/
!
)
Standard setting
-30 K
Setting range
-30 to +30 K
Frost protection temperature
The equipment enters reduced mode to protect itself against frost, as soon as
the average outside temperature drops below this value. This will be implemen-
ted independent of the setting of the operating mode selector.
The OFF point of the frost protection is set 2 K higher than the ON point.
A
Outside temperature
B
Frost protection temperature (can
be selected)
C
Frost protection OFF point (frost
protection tempe 2 K)
D
Reduced heating mode OFF
E
Reduced heating mode ON
Access
&
"
Device settings
"
&
"
Programming
"
&
"
System definition
"
&
"Frost protection T"
(
1
/
!
)
Standard setting
1 °C
Setting range
-15 to +15 °C
Temperature limit for reduced temperature mode
136
Control unit settings - system definition
55
92
968
GB
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...