With activated power-OFF ("power-OFF: YES") the power supply utility can
switch off the
heat that is being generated
by the
heat pump
. This requires
that the power-OFF contact has been connected (see page 81).
The
heat distribution
by the heating circuit pump and the circulation pump for
cylinder heating are not affected by the power interruption.
If power-OFF has been activated, a buffer cylinder must be installed to cover
the periods during which no heat can be generated.
Note
The effect of the power interruption on the
instantaneous heating water hea-
ter
is determined separately (see page 142).
Access
&
"Device settings"
&
"Programming"
&
"Heat pump"
&
"Power-OFF"
("YES"/"NO")
Standard setting
YES
Setting range
YES/NO
Maximum flow temperature
Setting the maximum heat pump flow temperature.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heat pump
"
&
"Max. flow temp."
(
1
/
!
)
Standard setting
60 °C
Setting range
25 to 60 °C
Minimum return temperature
Not the heat pump but the instantaneous heating water heater is started when
the actual temperature drops below the minimum return temperature.
The instantaneous heating water heater stays ON until the minimum return tem-
perature has been achieved.
Power-OFF compressor
137
Heat pump control settings
55
92
968
GB
Service
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...