The instantaneous heating water heater that is available as an accessory must
be activated by this parameter, if installed. Only that way can the instantaneous
heating water heater be regulated by the control unit.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Electric heater
"
&
"E heating"
("
YES
"/"
NO
")
Standard setting
NO
Setting range
YES/NO
Power-OFF; instantaneous heating water heater
This setting defines whether the power supply utility can shut off the power sup-
ply to the instantaneous heating water heater using a special control unit (set-
ting: "
YES
"). This requires that the power-OFF contact has been connected
(see page 81).
If the power supply utility is not to have this facility, select "
NO
".
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Electric heater
"
&
"Power-OFF"
("YES"/"NO")
Standard setting
YES
Setting range
YES/NO
Electric heating
This setting enables or disables the boosting of the heating circuits by the
instantaneous heating water heater.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Electric heater
"
&
"Heating with electric power"
("
YES
"/"
NO
")
Standard setting
YES
Setting range
YES/NO
E heating
142
Instantaneous heating water heater control settings
55
92
968
GB
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...