This function makes it possible to deactivate DHW heating using an integrated
instantaneous heating water heater that may be installed in the unit (e.g. if the
water is subsequently heated by an on-site instantaneous water heater).
The instantaneous heating water heater then only affects the heating circuit.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Electric heater
"
&
"DHW with electric power"
("
YES
"/"
NO
")
Standard setting
YES
Setting range
YES/NO
Maximum flow temperature
This determines the maximum flow temperature provided by the instantaneous
heating water heater.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Electric heater
"
&
"Max. flow temp."
(
1
/
!
)
Standard setting
65 °C
Setting range
5 to 75 °C
Heater rod delay
Adjustment of the time during which the electric heating is
not
switched ON
after changing the operating mode (reduced/standard).
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Electric heater
"
&
"Heater rod delay"
(
P
/
Q
)
Standard setting
0:30 h
Setting range
0:00 to 5:00 h
DHW with electric power
143
Instantaneous heating water heater control settings
55
92
968
GB
Service
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...