This setting determines whether the heat pump is used to dry the building as
well as the instantaneous heating water heater.
This function must be set to "
NO
" if the heat pump is not ready for operation
because the heat pump primary circuit is not ready when building drying takes
place.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Internal hydraulics
"
&
"HP for drying buildings"
("YES"/"NO")
Standard setting
NO
Setting range
YES/NO
Time for drying buildings
Selection of the number of days, during which the system for drying buildings is
to be used exclusively with the instantaneous heating water heater.
With this setting, the heat pump will not start.
Heating will be implemented in accordance with the settings for set temperature
and switching times for standard and reduced mode (see operating instruc-
tions).
The "
0
" setting switches this function OFF.
The remaining days for drying buildings will be shown on the display when the
programming unit flap is closed.
Note
If the "
Screed function
" (see page 162) has been activated, no intervention
must occur here.
The settings under "
Screed function
" are directly related to this setting. The
settings of both functions influence each other.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Internal hydraulics
"
&
"Time drying buildings"
(
j
/
k
)
Standard setting
0
(function
"
OFF
")
Setting range
0 to 30 days
Heat pump for drying buildings
145
Internal hydraulics control settings
55
92
968
GB
Service
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...