Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Excess reaction"
(
l
/
m
)
Standard setting
2
Setting range
0 to 2
Room temperature sensor
If a room temperature sensor is installed, it must be activated for the relevant
heating circuit.
For more information on the use of room temperature sensors and remote con-
trols, see page 77.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Room temperature sensor"
("
YES
"/"
NO
")
Standard setting
NO
Setting range
YES/NO
Slope; room temperature hook-up
The slope for room temperature hook-up can be selected, subject to a room
temperature sensor being installed and enabled and room temperature hook-up
being enabled (see page 158).
The higher the selected value, the greater the influence of the room tempera-
ture.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Heat. room hook-up"
(
l
/
m
)
Standard setting
10
Setting range
0 to 10
Excess reaction
(cont.)
157
Heating circuit control settings
55
92
968
GB
Service