A
Mixer permanently closed
B
Mixer closes (modulating)
C
Dead zone, mixer motor at zero
volt
D
Mixer opens
E
Mixer permanently open
T
V
Flow temperature
T
Vs
Set flow temperature
Δ
T
Vh
Active zone
Δ
T
Vt
Dead zone
t
Time
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Mixer active zone"
(
5
/
%
)
or
"Mixer dead zone"
(
=
/
0
)
Standard setting
Setting range
"
Mixer active zone
"
4.0 K
2.0 to 40.0 K
"
Mixer dead zone
"
1.0 K
0.5 to 3.0 K
Natural cooling
If all on-site components for the natural cooling function are installed, the sys-
tem definition must be extended to be able to use that function.
This setting can also be effected via the system configuration (see page 103).
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
Natural cooling
("
YES
"/"
NO
")
Standard setting
NO
Setting range
YES/NO
Mixer active zone/dead zone
(cont.)
164
Heating circuit control settings
55
92
968
GB