Setting and test values
Set value
Commis-
sioning
Heat pump cylinder heating
Temperature "
Secondary flow
"
°C
increasing
from:
to:
Temperature "
DHW cylinder top
"
°C
increasing
from:
to:
Control parameter report
Setting parameters
Setting range
Standard
setting
Commission-
ing
System definition
System scheme
0, 1 to 6 and F
*
1
2
Language
*
2
Deutsch
Power-OFF contact:
1S
No/Yes
No
Average time; outside
temperature
00:10 to 100:00 h
22:00 h
Heating limit < T room
0 to 20 K
4 K
Temperature limit for
red. Operating mode
-30 to 30 K
–
30 K
Frost protection tem-
perature
-15 to 15 °C
1 °C
Heat pump
Power-OFF
No/Yes
Yes
Max. flow temperature
25 to 60 °C
60 °C
Min. return tempera-
ture
1 to 40 °C
5 °C
Hysteresis T brine
1 to 20 K
5 K
Min. T primary in
-10 to 20 °C
–
4 °C
Min. runtime
2:00 to 30:00 min
2:00 minutes
Min. compressor off
00:20 to 30:00 min
10:00 min-
utes
Primary pump flow
00:10 to 16:40 min
2:00 minutes
Secondary pump flow
00:10 to 16:40 min
2:00 minutes
Optimum runtime
00:20 to 24:00 h
2:00 h
Instantaneous heating water heater
Electric heater
No/Yes
No
Hydraulic parameter report
(cont.)
191
Commissioning/service reports
55
92
968
GB
Service
*1
See page 10 and 103.
*2
German; English; French; Italian; Swedish; Dutch; Finnish; Polish.
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...