Please note
If the compressor is at a steep angle in the heat pump module, the intro-
duction of lubricant into the refrigerant circuit will damage the equipment.
The heat pump module must not be tilted more than 30° during installa-
tion.
1.
Remove the front part of the ther-
mal insulation.
2.
Remove the top part of the ther-
mal insulation.
3.
Insert the strain relief with
inserted cables (lying at the bot-
tom of the thermal insulation) into
the groove of the recess in the
lower part of the thermal insula-
tion.
4.
Check the floor area, valves and
all visible solder joints of the heat
pump for traces of oil.
Note
Traces of oil indicate a leaking
refrigerant circuit. Ask a refrigera-
tion engineer to check the heat
pump.
5.
Lead the thermal insulation
A
of
the primary inlets and outlets
through the openings in the top
part of the thermal insulation
B
.
Position the top part of the ther-
mal insulation.
Note
Do not push the thermal insula-
tion together when doing this.
Installing the heat pump module and making the . . .
(cont.)
64
Installation sequence
55
92
968
GB
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...